The combination of HecoFill limit value probe and Level Controller (NK) for fail-safe control and monitoring of limit levels in the tank.

The combination of Level Controller (NK) and HecoFill limit value probe sets standards and offers a high degree of safety during the storage and transfer of hazardous liquids.

This is due to the fact that level controller and limit value probe form an Ex-intrinsically safe circuit, work in a fail-safe mode and can be universally supplied. The limit probe is approved for use in zone 0. The permanent self-surveillance with liquid-analogue remote check up to the probe tip ensures a reliable surveillance of liquid limit levels.

The devices and probes are ATEX-approved and meet the requirements of the KVU (CH) as special fill protections and of the WHG (D) as overfill protection.

Data Sheet: HecoFill Probe & Level Controller NK411/NK412 (614 KB)

Your Benefits

  • High degree of safety by permanent self-monitoring
  • Independent of medium, density, conductivity or temperature
  • No calibration required
  • Almost maintenance-free as there are no movable parts in the tank resp. probe
  • Wide application range

Typical Applications

  • Tanks / manholes
  • Depots / collection trays
  • Process technology

Technical Data

Electrical connection A - blue
B - black
C - green
Probe connection via 3-pole probe cable 3 x 0.75 mm², blue that meets the following conditions:
Wire diameter: ≥ 0.1 mm, test voltage: ≥ 500 V, insulation thickness: ≥ 0.2 mm
Device connection Hectronic Controllers NK 311/312/313/411/412 (HecoFill HL and HH)
Isolating switch amplifi er (NAMUR) according to EN 60947-5-6
Probe circuit Intrinsically safe [Ex ia Ga] IIC
Environmental temperature EX: -20 °C to +60 °C/NON-EX: -30 °C to +80 °C

Technical Data - Level Controller NK

Supply network 20 to 253 VAC, 50 to 60 Hz, 2 W
22 to 253 VDC
Connection Screw terminals, max. 2.5 mm²
Environmental temperature -25 °C to +60 °C
Environmental conditions Use inside buildings
Installation location up to 2,000 m altitude
Relative humidity 25 to 95 % (non-condensing)
Pollution degree 2 (according to EN 61010)
Carrier rail housing Protection class: IP20
Material: ABS
Dimensions: W 35 mm, H 100 mm, D 115 mm
Approvals IECEx, ATEX, KVU, WHG

Variations

  • HecoFill Limit Probe
    Optoelectronic measuring principle for the surveillance of liquid limit levels in the tank
  • HecoFill Leak Probe
    Valuable for damage prevention: Detection of leaks in tanks, conduits or shafts For installation in tank rooms, collection trays for pipings or in dome shafts